Low-enthalpy geothermal resource evaluation through simulations of optimal geothermal heat pump systems : 지열히트펌프시스템의 최적 설계를 통한 저온지열자원의 활용성 평가

DC Field Value Language
dc.contributor.advisor이강근-
dc.contributor.author김성균-
dc.date.accessioned2017-07-14T00:36:38Z-
dc.date.available2017-07-14T00:36:38Z-
dc.date.issued2015-02-
dc.identifier.other000000025255-
dc.identifier.urihttps://hdl.handle.net/10371/121217-
dc.description학위논문 (박사)-- 서울대학교 대학원 : 지구환경과학부, 2015. 2. 이강근.-
dc.description.abstractSimulation models for evaluating utilization of low-enthalpy geothermal resources through the optimally designed geothermal heat pump (GHP) system is suggested. Firstly, a numerical model for the simulation of temperature changes in a borehole heat exchanger (BHE) with fluid circulating through U-tubes is developed. The model can calculate the thermal energy transferred from heat pumps to BHEs while considering the nonlinear relationship between temperature of the circulating fluid and the thermal energy. The use of the developed model enables also the design of a GHP system with the view of pursuing efficiency and financial benefit. The developed model is validated by comparing two measurement datasets with their respective simulation results. In addition, it is used to analyze the sensitivities of design parameters that can affect the performance of the closed-loop GHP system. The most sensitive parameters on the system are the thermal conductivity of the ground and the Darcian groundwater velocity considering acceptable distribution range in the realm of nature. Maximum change of the circulating fluid temperature at the BHE outlet is about 4℃ when thermal conductivity of the ground changes from 2 W/mK to 5 W/mK and the Darcian groundwater velocity changes from 10-8 m/s to 10-6 m/s, respectively. The numerical evaluation of a real GHP system with 28 BHEs and 79 heat pumps involves consideration of the base case and modified cases. In all cases, the temperatures of the circulating fluid at the BHE inlet and outlet, heat pump efficiency, and the heating power and electric power of heat pumps are obtained. The most cost-effective system in this case is for there to be 4, 6, and 6 BHEs on the first, second, and third floors, respectively.
The next version of the numerical simulator and grid generator is developed to consider multiple BHEs simultaneously. Thus, massively parallel computing procedures into the simulator are introduced to improve distributing memory requirements and computational efficiency for solving large simulation problems with a great number of grid-blocks. The new grid generator is designed to produce a simulation domain with multiple BHEs. The newly developed simulation model can consider thermal interactions among BHEs when the system is in operation and storing thermal energy in the ground after the operation period of the system. These two mechanisms should be considered in the evaluation of long-term performance of the BHE. The developed simulation model is tested for the performance improvement through parallelization. The computational efficiency of the developed simulation model is considerably increased in direct proportion to the number of the processors. The model is then applied to evaluate the performance of the KIGAM GHP system for a 25-year operation. The temperature of the ground in the vicinity of BHEs is gradually increased with time because of the imbalance of the injected/extracted thermal power to/from the ground during the cooling/heating seasons. It causes the decrease of the efficiency of the system during the cooling seasons for the long-term operation.
Finally, a versatile simulation model is developed to simulate not only the vertical closed-loop GHP system, but also the standing column well and open-loop GHP systems. A method to generate an unstructured Voronoi grid for its use in simulations of geothermal heat pump systems is presented. A series of codes is developed to create Voronoi cell center points that are placed at specific positions for well- or pipe-shaped Voronoi grids, to generate a three-dimensional grid from generated Voronoi cell vertices, and to visualize the generated grid and simulation results by ParaView. AMESH program is used to calculate the x- and y-coordinates of the Voronoi cell vertices from the Voronoi cell center points. The developed series of codes can generate the desired form of the grid. The generated grid is tested with confidence through simulations of water production/injection from/to the various kinds of the geothermal wells.
-
dc.description.tableofcontentsAbstract i
Contents iv
List of Tables vii
List of Figures viii

Chapter 1. Introduction 1
1.1. Backgrounds 1
1.2. Objectives 6

Chapter 2. Simulation modeling of a borehole heat exchanger 10
2.1. Introduction 10
2.2. Method 11
2.2.1. Physical background 11
2.2.2. Simulation model development 12
2.3. Study area 20
2.4. Model setup and validation 25
2.4.1. Model setup 25
2.4.2. Model validation 26
2.5. Sensitivity analysis 31
2.6. BHE design evaluation 33
2.6.1. Criteria and guidelines for the design evaluation 34
2.6.2. Simulation results for the base case 36
2.6.3. Simulation results for the modified cases 40
2.6.4. Cost analysis 44
2.7. Summary and conclusion 46

Chapter 3. Simulation modeling of multiple borehole heat exchangers 48
3.1. Introduction 48
3.2. Method 49
3.3. Speedup test 60
3.4. Evaluation of the long-term performance of the KIGAM GHP system 62
3.4.1. Study area 62
3.4.2. Model setup 64
3.4.3. Guidelines 66
3.4.4. Results and discussion 69
3.5. Summary and conclusion 75

Chapter 4. Voronoi grid for simulation of geothermal heat pump systems 77
4.1. Introduction 77
4.2. Method 83
4.3. Results 89
3.4.1. Examples of generated grids 89
3.4.1. Examples of generated grids 92
4.4. Conclusion 100

Chapter 5. Discussion 102

Chapter 6. Summary and conclusions 105

References 107

Abstract (in Korean) 115
-
dc.formatapplication/pdf-
dc.format.extent5297267 bytes-
dc.format.mediumapplication/pdf-
dc.language.isoen-
dc.publisher서울대학교 대학원-
dc.subjectgeothermal heat pump-
dc.subjectborehole heat exchanger-
dc.subjectdesign optimization-
dc.subjectlong-term performance-
dc.subjectTOUGH2-
dc.subjectintegral finite difference method-
dc.subject.ddc550-
dc.titleLow-enthalpy geothermal resource evaluation through simulations of optimal geothermal heat pump systems-
dc.title.alternative지열히트펌프시스템의 최적 설계를 통한 저온지열자원의 활용성 평가-
dc.typeThesis-
dc.contributor.AlternativeAuthorSeong-Kyun Kim-
dc.description.degreeDoctor-
dc.citation.pagesx, 117-
dc.contributor.affiliation자연과학대학 지구환경과학부-
dc.date.awarded2015-02-
Appears in Collections:
Files in This Item:

Altmetrics

Item View & Download Count

  • mendeley

Items in S-Space are protected by copyright, with all rights reserved, unless otherwise indicated.

Share